SILASmv control unit

A7-37S2-2111/.730
Features
- Black box system
- Automatic calculation of the purge time
- WEB interface
- 3 x PT100/1000 inputs
Marking
ATEX: II 3G Ex ec mc ic [ic pzc] IIC T4 Gb
II 3D Ex tc [ic pzc] IIIC T130 °C Db
IECEx:
Ex ec mc ic [ic pzc] IIC T4 Gb
Ex tc [ic pzc] IIIC T130 °C Db
Guidelines/Norms
Directive 2014/30/EU
Directive 2014/34/EU
Ambient temperature
In storage
-20 °C to +60 °C
During operation
-25 °C to +50 °C
Description
The SILASsup>mv Ex p control unit controls and monitors the pre-purge and operating phase of small, separate, pressurised enclosure equipment protected in accordance with ignition protection type pz. The parameters can be set using the integrated WEB interface or the optionally available p operator panel.
The SILASsup>mv features two release relays; one which is energised and one which has floating contacts. Two signal relays with one changeover contact each are additionally available. Three PT100/1000 inputs are available to monitor the temperature of the Ex p-protected equipment. Up to three switch values can be assigned to them. The design of the SILASsup>mv means that all components required for the pressurised enclosure are located in the control unit. The equipment to be monitored is connected to the Ex p control unit by means of a pipe, which allows a maximum purge volume of 70 litres.
The following components can also be connected:
- There is the option to connect a p operator panel
Technical data *
Protection class | IP 66 according to EN/IEC 60529 IP 64 according to EN/IEC 60079-0 |
Material | V4A stainless steel |
Weight | 6.8 kg |
*Refer to the documentation for more detailed information