ComExflex Potentiometer
for Local Control Stations and control Panels


07-3373-4D.0
Features
- One module for all fields of application
- High flexibility thanks to the junction box
- Low installation depth
Certification
CML 17 ATEX 1119 U
IECEx CML 17.0057U
CSA 2661552
CCC 2020322304000963
TC RU C-DE.BH02.B.00177
UL-BR 14.0133U
KCS KTL 12-KB4BO-0227U
Marking
ATEX: II 2G Ex db eb IIC Gb
I M2 Ex db eb I Mb
IECEx:
Ex db eb IIC Gb
Ex db eb I Mb
Ambient temperature
-55 °C to +60 °C
Description
The ComExflex potentiometer is used in almost all hazardous (potentially explosive) areas where machine functions are controlled by means of adjustable voltage distributors.
The module can be combined with a potentiometer actuator (scale graduation 0 to 10). A junction box is available as a safe and convenient means of installing the potentiometer in a control panel.
The conductors are connected by means of terminals on the back of the module which have an increased safety level. The easy installation of the potentiometer actuating element without the need for tools,ensures conformance to the high IP degree of protection.
Hinweis für Installations- und Revisonsarbeiten
Bei Bemessungsspannung:- ≤ AC 50 V/≤ DC 120 V (Safety extra low voltage in conformance to DIN VDE 0100 T. 410), The potentiometer drive shaft can be operated without an actuator.
- ≥ AC 50 V to max. AC/DC 230 V, Potentiometer drive shaft must be operated with an actuator or disconnected from voltage.
Technical data *
Protection class | determined by the actuating element and control station enclosure, min. IP 66, terminals IP 20 (IEC 60529) |
Dimensions | see data sheet |
Material | Enclosure material: Thermoplastic Resistance material: Carbon layer on ceramics |
Mechanical life | 25000 sinusoidal cycles |
Storage temperature | -55 °C to +70 °C |
Weight | approx. 110 g |
Voltage | Rated insulation voltage: 500 V Max. rated: operating voltage AC/DC 230 V |
Power | max. 1 W for Ta ≤ +40 °C |
Resistance | Resistance levels: 1 kOhm to 10 kOhm Curve shape: linear Resistance tolerance: + 20 % |
Connection | double terminals 2 x 2.5 mm², fine-stranded |
*Refer to the documentation for more detailed information