Attention: Our e-mail addresses with the domain bartec-benke.de has changed to bartec.com!

Bushing explosion-proof and pressure-sealed


07-96**-****/*****
Marking
ATEX: II 1/II 2G Ex d + e/d IIC Ga/Gb
I M1 Ex d + e I Ma
IECEx:
Ex d + e/d IIC Ga/Gb
Ex d + e I Ma
Ambient temperature
Temperature at rated operation:
-55 °C to +150 °C (with potting)
-55 °C to +200 °C (without potting)
depending on the lead used and type of sealing
Description
The 07-96..-.. type series II 1G line bushing serves as a gas diffusion-proof isolation element for zone 0 (1G/2G) while simultaneously providing an electric connection for leads:
- between flameproof enclosures
- between flameproof enclosures and enclosures with another approved type of protection Category II 2 G
- flameproof enclosures and protected installations Category II 3 G or
- in the safe area
Technical data *
Protection class | IEC 60529/EN 60529 without encapsulating IP 00 |
Material | Sleeve: metal Insulator: glass Pour: EP resin, PU resin Bushing bolt: FeNi alloy steel, Niro steel |
Pressure | -500 mbar to +400 bar depending on the design |
Installation | Diameter flansch: Ø 10 mm to 250 mm Thread size: M10 x 1 to M72 x 2 |
Voltage | ≤ AC 50 V/DC 75 V, 250 V, 690 V, 1 000 V |
Current | up to 500 A |
Connection | Core wires: 0.25 mm² to 16 mm² Threaded bolts: M3 to M30 (max. quantity of connections: 99) |
*Refer to the documentation for more detailed information